Archi-Civilarchi-civil.com
Historic Structures · TAR-01  |  Confidence: A (verified against the official text)
Figures are produced by engine/masonry.js and pinned in tests/masonry.test.js.

Home / Articles / Historic Structures TAR-01

What Do You Do When the Code Excludes Your Building?

A seismic code places registered heritage structures outside its scope in two separate clauses. That is not a gap — the same code says, one clause later, what to do instead. Worked through on twenty-six masonry piers of a registered school building.

Confidence: A Engine: engine/masonry.js Tests: tests/masonry.test.js — 38/38 Reading: ~17 min Last verified: 2026-09-10 Türkçe: bu yazının Türkçesi
How to read this article outside Turkey The clauses quoted here come from the Turkish seismic code (TBDY 2018), and the clause numbers are of course specific to it. The problem is not. Most national codes exclude registered heritage structures from their scope, and the engineer is then left with the same question: by what authority do you assess the building at all, and how must the result be described? This article treats the Turkish code as one worked example of how a code handles that situation — not as a rule to be transferred. What is transferable is the principle in section 9: when you are outside the scope, there is no rule to hide behind.
Correction — 2026-09-10 Section 8 of this article decomposed the effective divisor 2.222 as γm = 2.0 times an effective area factor of about 0.9. That reading was wrong. The header of the source data file states plainly κ = 0.90 | γ_M = 2.0; that is, 2.222 = γM ⁄ κ — dividing by the material factor and multiplying by the knowledge level factor at the same time. The second reduction is not an area factor but the knowledge level factor.

This does not change the article's thesis — two separate decisions are still buried in one number. But what the decomposition is does change, and more importantly: this is precisely the "mixing two conventions" case described in the abstract in TAR-02. The source calculation applies the new-design convention (dividing by γM) and the existing-building convention (multiplying by κ) together — whereas TBDY Clause 15.2.12(b) says that in existing-building assessment the material strengths shall not be divided by the material factor.

1. Two sentences

In the scope section of the code there is a clause most engineers have never read:

TBDY 2018 — Clause 1.1.8 The assessment and strengthening of registered structures and monuments of historical and cultural value, under earthquake effects, is outside the scope of this Code.

The same provision is repeated at the head of the chapter governing the assessment of existing buildings (Clause 15.1.5), which also excludes non-building structures.

So for a registered structure, carrying out a performance assessment under that chapter and declaring "the building is at the controlled damage level according to the Code" is, in the Code's own words, not possible. The Code does not assess that building.

2. So what do you do?

Up to here the situation is usually known, and most discussions stall right there: "if the code doesn't cover it, what do we do?" Yet the answer sits one line after the exclusion.

TBDY 2018 — Clause 1.1.9 For buildings and building-type structures outside the scope of this Code, until their own specific regulations are issued, the provisions of the relevant Turkish Standards may be used together with internationally accepted equivalent standards, codes or technical rules established by the relevant institutions, observing the principles set out in this Code.

That clause says three things, and all three matter:

  1. The gap is temporary. "Until their own specific regulations are issued" — one day there will be some; for now there are not.
  2. There is an order of precedence. First the relevant national standards, then internationally accepted equivalent provisions.
  3. The freedom is conditional. "Observing the principles set out in this Code" — you cannot do as you please; you remain bound to the Code's principles.

So using the code's masonry relations on a registered structure is not forbidden. But it is a choice, and the choice itself must be stated in the report.

3. Why does this matter?

What the distinction is worth in practice There is a large legal and professional difference between "assessed in accordance with Chapter 15 of the Code" and "this structure lies outside the Code's scope and has been assessed using the Code's masonry relations along the route opened by Clause 1.1.9". The first grants yourself an authority the Code did not give you.

There is a technical reason for the exclusion too. A code's masonry provisions are calibrated for regularly built, modern masonry buildings of known materials and regular plan. In a historic structure the wall section is usually layered — two dressed faces with rubble infill between — the mortar properties have changed over centuries, the geometry is irregular and the construction technique undocumented. Applying the same formula does not mean the formula's assumptions are satisfied.

4. A third scope limit

A less well known limit sits in the same chapter:

TBDY 2018 — Clause 15.1.6 Following an earthquake that has caused damage to a building, the seismic safety of the damaged building cannot be determined by the methods given in this Chapter.

So a building that has been through an earthquake and sustained damage cannot be assessed by the chapter's methods, registered or not. Taken together, a post-earthquake historic structure is outside the scope for two separate reasons.

5. Case: a registered school building

The figures below come from a real assessment: a registered primary school building, load-bearing masonry, three storeys. Section actions from a finite element model under elastic spectrum analysis; capacities from the code's masonry relations.

FieldValue
computing…
The scope status is written into the data set's own header and is carried by the engine with every result.

6. Shear strength and the forgotten cap

The characteristic shear strength of a wall is computed as:

fvk = fvk0 + 0.4 σd   ≤   0.10 fb fvk0: initial shear strength with no vertical stress · σd: mean vertical compressive stress · fb: unit (stone/brick) compressive strength. The friction term grows with vertical load — so shear strength falls in the upper storeys.
The part that gets skipped The relation has a cap: fvk cannot exceed one tenth of the unit compressive strength. In buildings with low-strength units this cap binds and cuts off the gain the friction term would otherwise provide. Our engine will not compute without fb; the cap cannot be skipped.

On this data set the engine reproduces all twenty-six published fvk values to within — — so the relation and its parameters have been recovered correctly.

7. Finding: shear governs everywhere

For each pier three failure modes were computed separately: shear, axial and flexural. The result is strikingly one-sided.

Failure modeGoverning inLargest DCRExceeding capacity
computing…
DCR = demand / capacity. Above 1 means the capacity is insufficient in that mode.
Findingcomputing…

The physical reason is plain: masonry is strong in compression and weak in shear. Vertical loads use only a small part of the wall section, while the horizontal seismic force bears directly on the shear strength — which comes only from mortar bond and friction.

A second pattern appears in the storey distribution:

StoreyPiersMean σdMean fvkInadequate
computing…
In the upper storeys the vertical load falls, so the friction contribution drops and the shear strength weakens.

8. Two decisions buried in one number

While reproducing the data a detail emerged. The effective divisor producing the published capacities is 2.222. Yet the code states the masonry partial factor explicitly: 1.75 for autoclaved aerated concrete and 2.0 for other materials.

2.222 = 2.0 × 1.111   =   γm × (1 / 0.9) The extra factor of 1.111 is a second reduction — for instance taking only 90% of the wall length as effective. The calculation is 11% more conservative, but because two decisions are buried in one number, it is invisible which came from where.
Principle Being conservative is not a fault. The fault is two separate engineering decisions disappearing inside a single number. The γm that comes from the code and the designer's own additional caution are different things: one is not open to discussion, the other is. Our engine takes them as separate inputs and reports them separately in the result.

9. What we can and cannot say

What we can say:

What we cannot say:

The correct wording The report sentence should look like this: "As the structure is registered, it falls outside the scope of the Code under Clauses 1.1.8 and 15.1.5. Following the route opened by Clause 1.1.9, and observing the principles set out in the Code, the Code's masonry relations have been used. The results are an engineering assessment, not a declaration of code compliance." That sentence is long, and that is precisely why it must be written.

10. How the engine carries the scope

The engine behind this article takes the scope status not as an optional note but as a required input. No calculation is performed until it is stated whether the structure is registered — and "I don't know" is not accepted either.

SituationEngine behaviour
Scope not statedThe calculation is refused.
Structure is registeredEvery result returns a scope note carrying the exclusion clauses and the route opened by Clause 1.1.9.
Damaged by an earthquakeClause 15.1.6 is added; the structure is outside scope for two reasons.
fb not givenThe calculation is refused, because the cap could not be applied.
γm and any extra reductionSeparate inputs; the effective divisor and its decomposition are reported.
Three failure modesAlways computed together; the largest DCR governs.
Scope is part of the calculation, not a footnote.

11. Test yourself

  1. Why is it wrong to carry out a performance assessment for a registered structure under the existing-buildings chapter and then declare the result?
  2. What three conditions does the fallback clause impose?
  3. Can a non-registered building damaged by an earthquake be assessed under that chapter?
  4. When does the cap in the shear strength relation bind? If it is skipped, in which direction is the answer wrong?
  5. What is the physical reason for the axial DCRs being low and the shear DCRs high in this building?
  6. A calculation reports an effective divisor of 2.222. Why does it matter to separate it into γm = 2.0 and an extra 1.111?
  7. Why does shear strength fall in the upper storeys?

References

  1. TBDY 2018 (Turkish Building Earthquake Code) — Clauses 1.1.8, 1.1.9, 11.2.9, 11.2.10, 11.2.11, 15.1.5, 15.1.6 and Eq.(11.1). Read directly from the full official text as published in the Official Gazette.
  2. Case data: finite element model and pier assessment of a registered primary school building; published with the permission of the data owner.
  3. For international practice in the assessment of historic structures, ICOMOS principles and the relevant national standards are among the sources the fallback clause points to.

All figures in this article are produced by engine/masonry.js and separately pinned in tests/masonry.test.js (38/38). The clause texts are quoted directly because the code is a publicly published regulation. Scope status is a required input in the engine and travels with every result.

Open the calculation tool → TAR-02: capacity convention → Türkçe okuyun →
archi-civil.com — What Do You Do When the Code Excludes Your Building? · TAR-01 · Confidence A · Printed:
A calculation on an out-of-scope structure is an engineering assessment, not a declaration of code compliance.