AISC 341-22 Special Moment Frame — Column–Beam Moment Ratio
§E3.4a strong-column/weak-beam: ΣM*pc/ΣM*pb > 1.0 (LRFD). Columns: Zc(Fyc − Prc/Ag), optionally projected to the beam centerline. Beams: AISC 358 probable moment Mpr = CprRyFyZe plus the shear-amplification moment Muv. Since AISC 341-16 the beam side uses Cpr — not the older 1.1RyFyZ. Turkish counterpart: ÇYTHYE/TBDY strong-column tools.
Column (same section above and below)
Beams
Results
Mpc per column · projection—
Cpr · Ry · Mpr AISC 358 §2.4.3—
Lh · Vpr · Muv—
ΣM*pc / ΣM*pb §E3.4a—
§E3.4aΣM*pc/ΣM*pb > 1.0; M*pc = Zc(Fyc − αsPrc/Ag) projected to the beam centerline (factor h/(h − db)); M*pb = Mpr + Muv at the column centerline
AISC 358Mpr = CprRyFyZe, Cpr = (Fy + Fu)/(2Fy) ≤ 1.2 (A992: 1.15); Vpr = 2Mpr/Lh + wuLh/2; Muv = Vpr(Sh + dc/2). Sh depends on the prequalified connection (RBS: a + b/2).
Table A3.2Ry: A992 and A572 Gr 50 = 1.1; A36 = 1.5
VerifyHand calculation (regression test): W24×76 beams both sides (Z = 200 in³), W14×257 column (Z = 487 in³, A = 75.6 in², d = 16.4 in), Pr = 600 kip, L = 30 ft, Sh = 11.95 in, wu = 1.2 kip/ft → Mpr = 12,650 kip-in, ratio = 1.406 (unprojected). Formulas: Elsevier, Results in Engineering (2022); Tekla; ideCAD.
ScopeLRFD only. The §E3.4a exceptions, panel-zone shear (§E3.6e), width-to-thickness limits (Table D1.1) and connection design (AISC 358) are separate checks.
Preliminary calculation tool. Final design requires the full text of the referenced standard (see the sources on this page) and review by a licensed PE.