ASCE 7-22 Diaphragm Seismic Design Forces

Three methods side by side: the traditional Fpx of §12.10.1–12.10.2, the alternative §12.10.3 procedure with the design acceleration coefficient Cpx and the diaphragm reduction factor Rs, and the §12.10.4 procedure for one-story rigid-wall, flexible-diaphragm (RWFD) buildings. Defaults reproduce the FEMA P-2192 examples.

Multi-story building (§12.10.1–2 and §12.10.3)

Levelh (ft)w (kips)FxTraditional FpxCpxAlternative FpxAlt. collector ×1.5

wpx is taken equal to wi (the FEMA example does the same "for simplicity"; walls parallel to the force may be excluded). Collectors with the traditional method use Ω0 (§12.10.2.1); with the alternative method ×1.5 (§12.10.3.4); neither needs to exceed Eci.

One-story RWFD building (§12.10.4)

Scope limits of §12.10.4.1 apply: one story; wood structural panel or bare (untopped) steel deck; rigid vertical elements (concrete, precast, masonry walls; steel or composite braced frames or walls); rectangular segments; no horizontal irregularities except Type 2. Defaults: FEMA P-2192 §7.6.2 warehouse (600 × 360 ft, SDS 1.0, SD1 0.5).

Sources and verification

MethodThe step-by-step procedures, the Rs table (ASCE 7-22 Table 12.10-1) and the zs table are taken from FEMA P-2192-V1, 2020 NEHRP Recommended Seismic Provisions: Design Examples (2021, public domain), §7.3. ASCE 7-22 is cited by clause number only.
AnchorsAll three FEMA P-2192 examples are reproduced (tests/asce7-diaphragm.test.js): one-story wood assembly hall (both methods govern at the lower bound, 19,072 / 17,072 lb); six-story steel building (traditional 302 / 510 / 460 / 411 / 377 / 377 kips; alternative roof 778 kips and floors 4–2 at 392 / 385 / 385 kips); one-story RWFD warehouse (traditional 1,712 kips; §12.10.4 with S400 detailing 1,266 kips; without it 3,800 kips — the detailing decision changes the force threefold).
Errata foundChecking the six-story example revealed two slips in FEMA P-2192 §7.5.2. (1) "Cpi = Cp0 = 0.48 (Eq. 12.10-8)" — Eq. 12.10-8 is 0.8·Cp0 = 0.384; the result is unaffected because 0.9·Γm1·Ω0·Cs = 0.51 governs. (2) At the 6th floor the book interpolates Cp6 over 12 ft (the story height) instead of the 0.2·hn = 14.4 ft between 0.8·hn and hn: 0.60 instead of 0.582, i.e. Fp6 = 471 instead of about 457 kips (conservative by 3 %). This tool uses the corrected interpolation. Also, the traditional Fpx is not floored at Fx: in a one-story building Fx = V includes the walls parallel to the force, which wpx excludes (FEMA §7.6.1 uses 1,712 kips, not V = 2,090).